Two-bus power flow by hand: a 138 kV line entered in ohms, checked against the closed-form voltage

ToolPower Flow Solver
Sourceoriginal
LevelUndergraduate

Problem

A 138 kV line with a series impedance of 4 + j32 Ω (line charging neglected) feeds a load of 90 MW and 40 Mvar from a source bus held at 1.00 pu. On a 100 MVA base, convert the line to per unit, solve the power flow by Newton-Raphson from a flat start, and check the load voltage against the closed-form solution of the two-bus problem.

Inputs to Enter

  • Base 100 MVA; branch data in ohms; Source: slack, 1.00 pu, 138 kV; Load: PQ, 90 MW, 40 Mvar, 138 kV
  • Line Source to Load: R 4 Ω, X 32 Ω, B 0, rating 150 MVA
Open the Power Flow Solver tool

Answers

  • Z base = 138² / 100 = 190.44 Ω; R = 4 / 190.44 = 0.02100 pu; X = 32 / 190.44 = 0.16803 pu; y = 0.7325 − j5.8597 pu
  • Iteration 1 from 1.0 ∠ 0°: ΔP = −0.9, ΔQ = −0.4; Jacobian [5.8597, 0.7325; −0.7325, 5.8597]; corrections Δδ = −0.14283 rad, Δ|V| = −0.08612
  • Largest mismatch 0.9, 0.0886, 0.00318, 4.5 × 10⁻⁶ pu: 3 iterations
  • Load bus 0.8903 pu (122.86 kV) at −9.231°; the quadratic u² + [2(PR + QX) − 1]u + (P² + Q²)(R² + X²) = 0 with u = |V|² gives the same 0.8903 pu
  • Source supplies 92.57 MW and 60.56 Mvar; the line loses 2.570 MW and absorbs 20.56 Mvar; flow 110.6 MVA, 73.7 % of the entered 150 MVA

Notes

Open this case in the tool: /analysis-tools/electrical/power-systems/power-flow/?try=two-bus-line-by-hand. Illustrative numbers. The closed form is in the method page; the test script compares the tool with it to nine decimals.