Tools › Building Systems › HVAC Equipment › Hydronic Pipe Sizing


Hydronic Pipe Sizing

Velocity, friction loss and pump head for the pipe segments of a hydronic (chilled- or hot-water) circuit: each segment takes a flow, a length, a nominal Schedule 40 steel size (or a custom inside diameter) and a sum of fitting loss coefficients; the tool computes the velocity, Reynolds number, Colebrook friction factor and head loss of each, checks them against the usual velocity and friction-rate limits, sums the series path to the pump head and gives the pump power. A friction chart for every standard size shows where each segment sits.

  • Darcy-Weisbach loss with the Colebrook friction factor and water properties at the entered temperature

  • Velocity and friction-rate check for each segment (noise, erosion, oversizing)

  • Pump head for the series path plus equipment head; hydraulic, shaft and motor power

  • Friction chart of the standard sizes with the segments marked

Hydronic Pipe Sizing


Unit System: /

Water, Pipe and Pump (temperature °F for USCS, °C for SI)






Pipe Segments (series path from the pump to the farthest load; first row is the pump flow)

1
2
3
4
5
×

Hydronic Pipe Sizing

Sizing Criteria

Hydronic pipe is sized between two limits. Too small and the friction rate and velocity climb: the pump head, the pump and the energy grow with them, and small pipe above about 4 ft/s (1.2 m/s) carries flow noise into occupied rooms. Too large and the pipe, insulation, hangers and the water volume cost more than they need to; below about 1 ft of water per 100 ft (100 Pa/m) with a low velocity the pipe is oversized, and very low velocities fail to carry air to the vents. The customary band is 1 to 4 ft of water per 100 ft of pipe, with velocity held under 4 ft/s in 2 in. and smaller and under 10 ft/s (3 m/s) in larger pipe against erosion of the elbows.

The loss is Darcy-Weisbach: h = (f L/D + ΣK) V²/(2g), head of water at the pipe's temperature. The friction factor f comes from the Colebrook equation at the segment's Reynolds number and relative roughness, 0.00015 ft (0.046 mm) for commercial steel, 0.000005 ft for copper and plastic; the tool iterates it to convergence. Fittings and valves are entered as a sum of loss coefficients K referred to the segment's velocity pressure.

The pump sees the series path to the farthest (critical) load: the sum of its segment losses plus the equipment head of that circuit, the coil or terminal, its control valve, the strainer and the chiller or boiler. Parallel branches that are not on the critical path do not add to the pump head; they are balanced to it. The pump flow is the first segment's flow. Hydraulic power is ρ g Q H; the shaft and motor powers follow from the efficiencies.

The friction chart draws every Schedule 40 size between 1 and 12 ft/s and marks the segments on it, which is the quickest way to see which segments to move a size up or down. Water properties are taken at the entered temperature: hot water is less viscous, so a heating system runs at a slightly lower friction factor than the same pipe on chilled water.




References

American Society of Heating, Refrigerating and Air-Conditioning Engineers (2021). ASHRAE Handbook: Fundamentals. ASHRAE, Peachtree Corners, GA.

Colebrook, C. F. (1939). "Turbulent flow in pipes, with particular reference to the transition region between the smooth and rough pipe laws." Journal of the Institution of Civil Engineers, Vol. 11, No. 4, pp. 133–156.

Crane Company (2013). Flow of Fluids Through Valves, Fittings, and Pipe. Technical Paper No. 410, Crane Co., Stamford, CT.


DISCLAIMER: The methods and calculation on aNOWysis.com are provided as means to educate the reader. There is no warranty, expessed or implied, as to the relevance or accuracy of the methods or calculations. All calculations should be checked by a qualified analyst for appropriateness and accuracy. We will not be held liable for any damages, injuries or deaths caused by using methods or calculations from this site.