Tools › Building Systems › Ducts and Airflow › Fitting Loss Coefficients


Fitting Loss Coefficients

The pressure loss of the fittings in a duct run, each from a catalog of loss coefficients of the common elbows, transitions, entries, exits, branches, dampers and grilles, applied to the velocity pressure of the air through it: Δp = C ρV²/2. Pick each fitting, give its count and the airflow and duct size it sits in, and the tool lists the coefficient, the velocity pressure and the loss, sums the run, and reports the equivalent length of each fitting in its duct so the losses can be carried into the Duct Sizing tool as a ΣC or an added length. The coefficients are representative values from the ASHRAE and SMACNA tables; the ASHRAE Duct Fitting Database gives the exact coefficient of a specific geometry.

  • Catalog of loss coefficients: round and rectangular elbows (radius, mitered, vaned), transitions, entries, exits, branches, dampers, grilles

  • Loss per fitting from its velocity pressure, count, and the total of the run

  • Equivalent length of each fitting in its own duct (friction factor from Colebrook), for the equal-friction method

Fitting Loss Coefficients


Unit System: /

Air


Fittings

1
2
3
4
×

Fitting Loss Coefficients

Loss Coefficients and Equivalent Length

Air turning a corner, changing area or splitting at a branch loses total pressure in proportion to its velocity pressure: Δp = C ρV²/2. The coefficient C is a property of the fitting's shape, nearly independent of velocity at duct Reynolds numbers, and is tabulated by ASHRAE (the Duct Fitting Database, several hundred geometries) and SMACNA. The catalog on this page holds representative values for the common fittings; a long-radius five-gore round elbow loses about a tenth of a velocity pressure, a mitered elbow without vanes more than a full one, and turning vanes bring the mitered elbow back to a tenth or a third depending on the vane type.

The velocity used is that in the duct where the fitting sits, or for a transition the smaller duct, and for a branch the branch velocity. Branch coefficients depend on the flow split; the values here are for a branch taking half the common flow.

The equivalent length is the straight run of the same duct with the same loss, Le = C D / f. It lets fitting losses be added to the duct lengths in the equal-friction method; because f varies with size and velocity, the equivalent length is computed for each row's own duct. The total of the run can also be entered in the Duct Sizing tool as each segment's ΣC.

Not included: system effect at the fan, the dependence of branch coefficients on the flow ratio, and the interaction of closely spaced fittings (two elbows within a few diameters lose more than their sum).




References

American Society of Heating, Refrigerating and Air-Conditioning Engineers (2021). ASHRAE Handbook: Fundamentals. ASHRAE, Peachtree Corners, GA.

Sheet Metal and Air Conditioning Contractors' National Association (2006). HVAC Systems Duct Design, 4th ed. SMACNA, Chantilly, VA.

Idelchik, I. E. (2008). Handbook of Hydraulic Resistance, 4th ed. Begell House, Redding, CT.


DISCLAIMER: The methods and calculation on aNOWysis.com are provided as means to educate the reader. There is no warranty, expessed or implied, as to the relevance or accuracy of the methods or calculations. All calculations should be checked by a qualified analyst for appropriateness and accuracy. We will not be held liable for any damages, injuries or deaths caused by using methods or calculations from this site.