Tools › Building Systems › Codes and Compliance › Envelope UA Compliance


Envelope UA Compliance

Building-envelope compliance by the total-UA trade-off used by the DOE REScheck and COMcheck programs: the sum of U-factor times area of every proposed assembly against the same sum at the required U-factors, per assembly and in total, with the window-to-wall ratio, the area-weighted U-factors and SHGC, and a slab-edge F-factor term. An assembly U-factor is built from its layers (series resistances with inside and outside films, a generic layer library of values printed in the ORNL Insulation Fact Sheet documentation, the REScheck technical support document and the Wood Handbook) by the parallel-path method of the REScheck technical support document (eq. A.1) with the ORNL reduced-clear-wall value beside it. A degree-day estimate gives the annual heating and cooling energy, fuel and cost from NCEI 1991 to 2020 normals of twelve stations (or entered degree days), infiltration, the design heat loss and the balance-point temperature, and the layer assembly is checked for condensation by the Glaser dew-point method (temperature and vapour-pressure profiles). The default is a 2,000 ft² single-storey house in Chicago (climate zone 5) with the required U-factors of the IECC U-factor table as reprinted by the DOE Building Energy Codes Program; the house itself is illustrative.

  • Total UA trade-off: Σ U A proposed ≤ Σ U A required (REScheck / COMcheck method), per assembly and in total, with the slab-edge F × P term, the window-to-wall ratio, area-weighted U and SHGC

  • Assembly U-factor from layers: series R with air films, the parallel-path framing correction (PNNL-14864 eq. A.1) and the ORNL clear-wall factor; required U-factors by climate zone as reprinted by DOE

  • Degree-day energy: Q = 24 UA HDD with infiltration, fuel use and cost (EIA heat contents), design heat loss, balance-point temperature; NCEI 1991 to 2020 normals of twelve stations

  • Glaser condensation check of the layer assembly: temperature, saturation and vapour-pressure profiles, the condensation plane and rate

Envelope UA Compliance


Unit System: /

Envelope assemblies (U in Btu/h·ft²·°F for USCS, W/m²·K for SI; a blank required U is filled from the climate-zone table below; SHGC for glazing only)

1
2
3
4
5

Climate zone and slab edge (F in Btu/h·ft·°F for USCS, W/m·K for SI; perimeter 0 omits the slab term)





Assembly U-factor from layers, inside first (thickness in in / mm; R: the rated R for insulation, the layer R or R per inch for an entered layer, in the selected system; permeance in perm for USCS, ng/(s·m²·Pa) for SI, blank = no vapour resistance)

1
2
3
4
5
6
7
8

Framing correction and where the layer U goes






Climate and operation (temperatures in °F for USCS, °C for SI; degree days base 65 °F / 18.3 °C; fuel energy in Btu per sold unit; money a plain number)















Condensation check of the layer assembly (Glaser method at the heating set point and the winter design temperature)



×

Envelope UA Compliance

UA Trade-Off, Layer U-Factors, Degree Days and the Glaser Method

Energy codes give two ways to show that a building's envelope is good enough: the prescriptive path, where every assembly meets the R-value or U-factor of a table, and the total-UA path, where the heat-loss coefficients of the whole envelope are added up and the sum must not exceed what the same building would have at the table values. The second is what the DOE's REScheck and COMcheck programs compute, and it is the method of this tool: an envelope with better walls and a worse floor can comply by trading one against the other. This page sets out the four calculations the tool makes, the sources of its constants, and what it does not do.

The total-UA comparison

For each assembly i with area Ai and overall U-factor Ui (inside and outside air films included, the whole-window value for fenestration), UAi = Ui Ai is the steady heat flow per degree of indoor-to-outdoor temperature difference. The proposed building complies by total UA when

Σ Up,i Ai ≤ Σ Ur,i Ai,

the right-hand side being the "code building": the same areas at the required U-factors. The REScheck user's guide describes exactly this: "a simple U-factor × Area (UA) calculation for each building assembly … if the total UA of your building is less than or equal to the total UA of the code building, your building complies". A slab-on-grade floor enters both sums as its F-factor (heat loss per unit length of exposed perimeter per degree) times the perimeter. The trade-off margin printed is (UAr − UAp)/UAr: positive when the envelope beats the code building. The tool also flags every row that exceeds its own requirement, because the prescriptive path would reject it and because a code may cap how far one assembly can be traded (the IECC, for instance, keeps mandatory fenestration U and SHGC backstops).

Three descriptive quantities come with the comparison. The area-weighted U, Σ U A / Σ A, over the whole envelope, the opaque part and the fenestration. The window-to-wall ratio, the area of windows and glazed or opaque doors over the gross wall area (net wall plus those openings); ASHRAE 90.1's prescriptive path and the commercial IECC limit it (40 % and 30 % in the editions the DOE COMcheck slides describe, with the limit tradable in some editions and hard in others), the residential IECC does not. And the area-weighted solar heat gain coefficient of the glazing against the area-weighted requirement, which is how the codes state their SHGC rule.

Required U-factors. The IECC and ASHRAE 90.1 tables are copyrighted and the tool does not ship them. It carries one table that a government publication reprints: slide 15 of the DOE Building Energy Codes Program deck Energy Code Compliance Paths (2019) shows IECC Table R402.1.4, the residential U-factor alternative, for the eight assembly columns and seven climate-zone rows. A blank required cell takes that value for the selected zone and type; a value typed in the cell always wins, so the analyst can enter the adopted edition's numbers (the 2021 IECC changed several fenestration and wall values, as the DOE's 2021 webinar slides list). The same slide prints the small worked example the tool reproduces: in zone 5 a framed wall at U 0.060 is R-16.67 overall; R-20 of cavity insulation alone would be 1/20 = 0.05 before sheathing and films are added.

An assembly U-factor from its layers

Through a layered assembly the resistances add: R = Rin film + Σ Rlayer + Rout film, U = 1/R. The ORNL Insulation Fact Sheet says so in one sentence, and warns in the next that framing bridges the insulation so the assembly's U is worse than the insulation's. The tool handles the framing by the parallel-path method of the REScheck technical support document (PNNL-14864-1-2, eq. A.1): the opaque area is split into a fraction f at the framing and 1 − f at the cavity, each path a series of resistances, and the paths add in parallel,

U = f / (Rcommon + Rframing) + (1 − f) / (Rcommon + Rcavity),

where Rcommon is every layer that both paths share (films, finishes, sheathing, continuous insulation), Rcavity the insulation or air in the stud space, and Rframing the wood across the same depth (the TSD uses 1.25 per inch: 4.38 for a 2×4, 6.88 for a 2×6). The TSD's framing fractions are 25 % of the opaque wall at 16 in on centre and 22 % at 24 in (from the 1993 ASHRAE Handbook), 7 % for ceiling joists at 24 in. The method is accurate unless a layer is highly conductive; steel studs short-circuit the insulation far more than their area suggests, and the TSD applies correction factors to the cavity R instead. For a metal-framed assembly use an entered U from a tested or modelled source, or the ORNL factor below as a rough figure.

Beside the parallel-path value the tool prints the ORNL fact-sheet shortcut (ORNL/TM-2008/017, Table 1): the "reduced clear wall" sums the layers from outside film to inside film, multiplies by 0.75 for wood framing or 0.40 for metal framing, and then adds any foam sheathing. It reproduces the fact sheet's own Table 9 composite U-values (a R-13 2×4 wall 0.0812, R-21 plus R-5 foam 0.0429) and is a check on the parallel path, not a replacement for it.

The layer library. Every value in the material list is printed in a public-domain document and is quoted in the units of its source (h·ft²·°F/Btu): the air films, gypsum board, plywood, siding and empty-cavity values of ORNL/TM-2008/017 Table 1 and of PNNL-14864-1-2 Tables A.1 and A.9, blown fiberglass at R-2.5 per inch (TSD, A.1.2), and wood at 12 % moisture content from the Wood Handbook's Table 4-7, whose values follow its eq. 4-15, k = G (B + C x) + A. Insulation is entered at its rated R (the fact sheet notes the FTC label requirement), continuous insulation likewise, and anything else (masonry, concrete, glass, metal, air spaces) is an entered layer: ASHRAE Fundamentals chapter 26 is where those tested values are read, and the tool does not reproduce its table. In SI the entered R-values are in m²·K/W and the library values are converted on the page.

Degree-day energy, design heat loss and the balance point

A heating degree day is the amount by which a day's mean temperature falls below the base, 65 °F (18.3 °C) in the NOAA normals; summed over a year it is a measure of how much heating the climate demands. If the building's loss were proportional to the indoor-outdoor difference and heating were needed whenever the outdoors fell below the base, the annual heating energy would be

Qh = 24 × UA × HDD,

with UA the sum of the envelope UA and the infiltration conductance. Infiltration carries ρ cp per unit volume of air exchanged: 0.018 Btu per ft³ per °F (0.075 lb/ft³ × 0.24 Btu/lb·°F, the familiar 1.08 Btu/h per cfm per °F) or 1.2 kg/m³ × 1,006 J/kg·K in SI, times the air changes per hour and the conditioned volume. The fuel input is Qh/η at the seasonal efficiency, converted to sold units with the EIA heat contents (a therm is 100,000 Btu by definition, electricity 3,412 Btu/kWh, heating oil 138,500 and propane 91,452 Btu per gallon) and priced. The cooling figure 24 × UA × CDD is the conduction and infiltration part only; the solar and internal gains that dominate a cooling load are outside this estimate, so it is a lower bound to be used for comparing envelopes, not for sizing.

The design heat loss is UA × (Tset − Tdesign) at the winter design temperature, the number a heating plant is sized to. The balance-point temperature Tbal = Tset − qint/UA is the outdoor temperature at which the internal gains alone hold the set point; above it no heating is needed. A well-insulated house with normal gains balances several degrees below 65 °F, and its true heating degree days are those at base Tbal, fewer than the published base-65 figure, which is why the degree-day estimate tends to overstate the heating of tight, well-insulated buildings. The station list fills the 1991–2020 NCEI normals (ANN-HTDD-NORMAL and ANN-CLDD-NORMAL of the by-station files) for twelve airports; any other site's values are entered from the same product.

The Glaser (dew-point) condensation check

Vapour diffuses through an assembly from the high-vapour-pressure side to the low, and condenses wherever the vapour pressure it would reach exceeds the saturation pressure at the local temperature. The Glaser construction makes the check in steady state: the temperature falls through the layers in proportion to their thermal resistance, the vapour pressure in proportion to their vapour resistance (the reciprocal of the permeance; a perm is one grain of water per hour per square foot per inch of mercury, 57.2 ng/(s·m²·Pa)), and the two profiles are compared interface by interface. Saturation pressure comes from the Hyland–Wexler equations of the site's psychrometric library, over ice below 0 °C. If the linear vapour-pressure line crosses the saturation curve, condensation forms at the interface where the excess is largest; the line is cut back to saturation there, and the rate of condensation is the vapour flux arriving from inside minus the flux leaving to the outside, each flux being a pressure difference over the vapour resistance of that side. The tool reports the plane, the rate and the amount accumulated over 30 days of design weather, the last as a comparison between designs: design conditions persist for days, and a seasonal moisture balance needs an hourly model with storage (NIST's MOIST program, SP 917, is the public-domain example).

Two rules from USDA Agriculture Information Bulletin 373 frame the result: a vapour retarder on the warm side should have 0.25 perm or less, and the cold-side layers should be at least five times more permeable than the warm side, so that what gets in can get out; a layer under 1 perm on the cold side traps the vapour. NIST SP 917 gives the permeances of finishes (latex paint 5 to 15 perm, oil paint 1 to 3, vapour-retarder paint under 1, vinyl wallpaper 0.5) that the tooltip repeats; the default plywood, foam and polyethylene entries are representative values and the adopted material data or ASHRAE Fundamentals chapter 26 should replace them in a real check. The dew point of the indoor air is printed as well: any surface colder than it, a window frame or a thermal bridge, condenses regardless of the wall's layers.

Reading the results and the limits

Table 1 is the compliance table: each row's UA, its own pass or fail, and the totals with the verdict. Figure 1 draws the two UA sets side by side so the trade is visible. Table 2 and the equations under it show how the layer U-factor was built; the value is written into the chosen assembly row when the box is ticked. Table 3 and Figures 2 and 3 are the condensation check: the dashed dew-point line of Figure 2 touching the temperature line, or a ratio above 1 in Table 3, means condensation at that interface. Table 4 is the annual estimate.

What the tool does not do: it is not REScheck or COMcheck and prints no certificate; the required values of an adopted edition, its mandatory backstops, its rules for crawl spaces, basements, raised trusses and steel framing, and its performance (simulation) path are the analyst's to apply. The parallel-path method is for wood framing; the ORNL metal factor is a rough figure. Thermal bridges at corners, band joists and window frames are not modelled. The degree-day method ignores solar gain, thermal mass and part-load equipment behaviour, and the Glaser check ignores moisture storage, air leakage (which moves far more moisture than diffusion), solar drying and the day-night cycle. Each is the standard first estimate, and each is reproduced in the test script from the public documents named above.




References

Stovall, T. K. (2008). Supporting Documentation for the 2008 Insulation Fact Sheet Update. ORNL/TM-2008/017, Oak Ridge National Laboratory, Oak Ridge, TN.

U.S. Department of Energy (2008). Insulation Fact Sheet. DOE/CE-0180, Office of Energy Efficiency and Renewable Energy, Washington, DC.

Pacific Northwest National Laboratory (2005). REScheck Technical Support Document. PNNL-14864-1-2, Pacific Northwest National Laboratory, Richland, WA.

U.S. Department of Energy, Building Energy Codes Program (2019). Energy Code Compliance Paths. Presentation slides, Pacific Northwest National Laboratory, Richland, WA.

U.S. Department of Energy, Building Energy Codes Program (2022). Residential Energy Code Compliance: REScheck Basics. National Energy Codes Conference bootcamp slides, Pacific Northwest National Laboratory, Richland, WA.

U.S. Department of Energy, Building Energy Codes Program (2008). REScheck Software User's Guide. Pacific Northwest National Laboratory, Richland, WA.

Salcido, V. R., Chen, Y., Xie, Y., and Taylor, Z. T. (2021). National Cost Effectiveness of the Residential Provisions of the 2021 IECC. PNNL-31019, Pacific Northwest National Laboratory, Richland, WA.

National Centers for Environmental Information (2021). U.S. Climate Normals 2020: U.S. Annual/Seasonal Climate Normals (1991–2020). National Oceanic and Atmospheric Administration, Asheville, NC.

Forest Products Laboratory (2010). Wood Handbook: Wood as an Engineering Material. General Technical Report FPL-GTR-190, U.S. Department of Agriculture, Forest Service, Madison, WI.

Burch, D. M., and Chi, J. (1997). MOIST: A PC Program for Predicting Heat and Moisture Transfer in Building Envelopes, Release 3.0. NIST Special Publication 917, National Institute of Standards and Technology, Gaithersburg, MD.

Anderson, L. O., and Sherwood, G. E. (1974). Condensation Problems in Your House: Prevention and Solution. Agriculture Information Bulletin 373, U.S. Department of Agriculture, Forest Service, Washington, DC.

U.S. Energy Information Administration (2024). Units and Calculators Explained: British Thermal Units (Btu). U.S. Energy Information Administration, Washington, DC.

Hyland, R. W., and Wexler, A. (1983). "Formulations for the Thermodynamic Properties of the Saturated Phases of H2O from 173.15 K to 473.15 K." ASHRAE Transactions, Vol. 89, No. 2A, pp. 500–519.

Glaser, H. (1959). "Graphisches Verfahren zur Untersuchung von Diffusionsvorgängen." Kältetechnik, Vol. 11, No. 10, pp. 345–349.

International Code Council (2021). International Energy Conservation Code. International Code Council, Washington, DC.

American Society of Heating, Refrigerating and Air-Conditioning Engineers (2022). ANSI/ASHRAE/IES Standard 90.1-2022: Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings. ASHRAE, Peachtree Corners, GA.

American Society of Heating, Refrigerating and Air-Conditioning Engineers (2021). ASHRAE Handbook: Fundamentals. ASHRAE, Peachtree Corners, GA.


DISCLAIMER: The methods and calculation on aNOWysis.com are provided as means to educate the reader. There is no warranty, expessed or implied, as to the relevance or accuracy of the methods or calculations. All calculations should be checked by a qualified analyst for appropriateness and accuracy. We will not be held liable for any damages, injuries or deaths caused by using methods or calculations from this site.