Gauss-Seidel against Newton-Raphson on a three-bus power flow: 20 sweeps against 3 iterations

ToolPower Flow Solver
Sourceoriginal
LevelUndergraduate

Problem

Solve the three-bus system of the previous example (slack at 1.04 pu, a PV bus generating 120 MW at 1.02 pu, a 250 MW + 110 Mvar load bus) by Gauss-Seidel with an acceleration factor of 1.6, stopping on the same test as Newton-Raphson (largest power mismatch below 0.0001 pu), and compare the number of iterations.

Inputs to Enter

  • Same buses and lines as the three-bus example; method Gauss-Seidel, acceleration factor 1.6, tolerance 0.0001 pu, flat start
  • Advanced: chart also shows the other method
Open the Power Flow Solver tool

Answers

  • Sweep 1, Hydro (PV): Q = −0.0948 pu from the starting voltages; computed voltage 1.02779 + j0.03108, reset to 1.02 ∠ 1.732°
  • Sweep 1, City (PQ): voltage 0.9575 pu at −6.943° after acceleration; largest mismatch after the sweep 1.181 pu
  • The mismatch falls by a factor of about 1.6 per sweep: 20 sweeps to reach 7.3 × 10⁻⁵ pu
  • Newton-Raphson on the same case: 2.296, 0.0962, 0.000629, 2.9 × 10⁻⁸ pu in 3 iterations
  • Both give City 0.9631 pu at −5.02° and a slack generation of 187.67 MW

Notes

Open this case in the tool: /analysis-tools/electrical/power-systems/power-flow/?try=gauss-seidel-against-newton. Illustrative numbers. On this page the acceleration factor is applied to PQ buses only and both methods stop on the largest power mismatch, so the counts are comparable; texts that stop Gauss-Seidel on the voltage change report other counts.