Tools › Electrical and Controls › Power Systems › Power Flow Solver › Example
IEEE 14-bus test case: Newton-Raphson power flow against the archive's stored solution
| Tool | Power Flow Solver |
| Source | University of Washington, Department of Electrical Engineering (1993). Power Systems Test Case Archive: 14 Bus Power Flow Test Case. IEEE Common Data Format file ieee14cdf.txt, Seattle, WA. |
| Level | Graduate |
Problem
The IEEE 14-bus test case (a 1962 portion of the American Electric Power system, 100 MVA base) has a slack bus at 1.060 pu, four voltage-controlled buses (2, 3, 6 and 8), nine load buses, 17 lines, three transformers with off-nominal taps and a 19 Mvar shunt at bus 9; the loads total 259.0 MW and 73.5 Mvar. Solve the power flow from a flat start and compare the voltages, the slack generation and the losses with the solution stored in the archive file.
Inputs to Enter
- Base 100 MVA; bus and branch data exactly as in the archive file (the tool's opening tables); generation 40 MW at bus 2
- Newton-Raphson, flat start, tolerance 0.0001 pu, reactive limits enforced
Answers
- 22 unknowns (13 angles, 9 magnitudes); Y(1,1) = 6.0250 − j19.4471 pu; first Jacobian entry ∂P2/∂δ2 = 32.728
- Largest mismatch: 0.9219 pu at the start, then 0.1005, 0.000710 and 6.0 × 10⁻⁸ pu: converged in 3 iterations
- Slack generation 232.39 MW and −16.55 Mvar (archive 232.4 MW, −16.9 Mvar); losses 272.39 − 259.00 = 13.39 MW (archive 13.4 MW)
- Bus 14: 1.0355 pu at −16.034° (archive 1.036 pu, −16.04°); bus 4: 1.0177 pu at −10.313° (archive 1.019 pu, −10.33°); lowest voltage the bus 3 set-point 1.010 pu
- Generator reactive outputs at buses 2, 3, 6, 8: 43.56, 25.08, 12.73, 17.62 Mvar (archive 42.4, 23.4, 12.2, 17.4 Mvar)
- Line 1–2 carries 156.88 MW and −20.40 Mvar from bus 1 and loses 4.298 MW
Notes
The tool opens on this case; press Submit, or open it in the tool: /analysis-tools/electrical/power-systems/power-flow/?try=ieee-14-bus. The archive's stored solution is printed to three decimals of voltage and one of power and is not exactly the converged solution of its own data: voltages agree within 0.0013 pu and 0.02°, reactive outputs within 1.7 Mvar. An independent numpy implementation reproduces the tool's values (test_power_flow.php).
More Examples for This Tool
- Two-bus power flow by hand: a 138 kV line entered in ohms, checked against the closed-form voltage
- Three-bus power flow with a slack, a PV and a PQ bus: mismatches, Jacobian and corrections of the first iteration
- IEEE 14-bus case with a generator on its reactive limit: bus 2 held at 30 Mvar and its voltage released
- Gauss-Seidel against Newton-Raphson on a three-bus power flow: 20 sweeps against 3 iterations