Tools › Electrical and Controls › Power Systems › Power Flow Solver › Example

IEEE 14-bus case with a generator on its reactive limit: bus 2 held at 30 Mvar and its voltage released

ToolPower Flow Solver
SourceUniversity of Washington, Department of Electrical Engineering (1993). Power Systems Test Case Archive: 14 Bus Power Flow Test Case. IEEE Common Data Format file ieee14cdf.txt, Seattle, WA. The reactive limit of bus 2 is lowered from the file's 50 Mvar to 30 Mvar for this example.
LevelGraduate

Problem

In the IEEE 14-bus case the generator at bus 2 needs 43.56 Mvar to hold 1.045 pu. Lower its upper reactive limit to 30 Mvar and solve again: which bus changes type, where does its voltage settle, and which machines make up the reactive power?

Inputs to Enter

  • IEEE 14-bus data with Q max of bus 2 set to 30 Mvar; Newton-Raphson, flat start, reactive limits enforced
Open the Power Flow Solver tool

Answers

  • Iterations 1 to 3 converge with bus 2 as a PV bus needing 43.56 Mvar, above the 30 Mvar limit
  • Bus 2 becomes a PQ bus at 30 Mvar (23 unknowns); the mismatch jumps to 0.1356 pu (the 13.56 Mvar withheld) and falls to 1.4 × 10⁻⁸ pu in two more iterations: 5 in all
  • Bus 2 settles at 1.0405 pu instead of 1.045 pu; bus 4 at 1.0159 pu, bus 5 at 1.0177 pu
  • Reactive output moves to the other machines: slack −7.82 Mvar (was −16.55), bus 3 28.53 (was 25.08), bus 6 13.82 (was 12.73), bus 8 18.12 Mvar (was 17.62)
  • Slack real power 232.40 MW; losses 13.40 MW (13.39 MW before)

Notes

Open this case in the tool: /analysis-tools/electrical/power-systems/power-flow/?try=generator-on-reactive-limit. The limit value is illustrative; the rest is the archive data. Checked against an independent numpy implementation that applies the same switching rule (test_power_flow.php).

More Examples for This Tool