Tools › Building Systems › Lighting and Electrical › Cable Pulling Tension


Cable Pulling Tension

Enter the cable, the conduit and the run as a list of straights and bends; get the pulling tension at the end of every segment for a pull from each end, the sidewall pressure at every bend, the weight correction factor and the jam ratio, with the run and the tension along it drawn for both directions. The page sets the computed figures beside the allowable tension and sidewall pressure typed in from the cable maker's data; it does not judge a pull, and the pulling equipment, the cable maker's limits and the adopted electrical code are outside it.

  • Tension segment by segment for a pull from end A and from end B, drawn against distance with the entered allowable

  • Level and sloping straights, horizontal bends with the cable weight included, vertical bends turning up or down

  • Sidewall pressure at every bend, weight correction factor for one cable or three (cradled or triangular), jam ratio

  • One straight and one bend worked as formula, numbers, answer; U.S. or SI units

Cable Pulling Tension


Unit System: /

/

Cable and conduit








Limits from the cable maker and the reel




Run from end A to end B (one row per straight or bend)

1
2
3
4
5

Jam ratio and bend equation





×

Cable Pulling Tension

Cable Pulling Tension: Straights Add, Bends Multiply

The tool takes a cable, a conduit and a run described as a list of straights and bends, and works out the tension in the cable at the end of every segment for a pull from either end, with the pressure the cable puts on the wall of every bend. It sets those figures beside the allowable tension and sidewall pressure typed in from the cable maker's data; it does not judge a pull.

The idea: where a bend sits matters more than how many there are

Dragging a cable along a straight conduit is dragging a weight along a floor: every foot adds the same friction, whatever the tension already is. A bend is different. The cable is held against the inside of the curve by its own tension, so the friction in a bend grows with the tension that arrives there. A straight adds to the tension; a bend multiplies it.

A conduit run with a long straight followed by two quarter bends near end B, drawn in plan, and under it the cable tension against distance for a pull from A to B and from B to A
Figure 1: Three cables in a run of 350 ft, a quarter bend, 40 ft, a quarter bend and 15 ft (an illustrative case). Pulled from A to B the long straight builds the tension first and both bends multiply it; pulled from B to A the bends act on a small tension and the straight is added last.

That is why the same run can need several times the pull in one direction as in the other, and why the tool always works both.

The equations

Symbols: T tension, Wt weight of all the cables per unit length, L length of a straight, θ its slope above the horizontal, μ coefficient of friction, Kw weight correction factor, φ angle of a bend in radians, R its radius, d cable diameter, D conduit inside diameter.

Segment or quantityFormulaWhere it comes from
Straight, levelTout = Tin + μ Kw Wt Lfriction on the weight
Straight, rising at θTout = Tin + Wt L (sin θ + μ Kw cos θ)the weight along the slope is lifted; the weight across it gives friction
Straight, falling at θTout = Tin − Wt L (sin θ − μ Kw cos θ), not below zerothe weight along the slope helps the pull
Horizontal bend, with the cable weightTout = Tin cosh(μ Kw φ) + √(Tin² + (Wt R)²) sinh(μ Kw φ)wall force per length √((T/R)² + Wt²): tension sideways, weight downward
Horizontal bend, capstan formTout = Tin eμ Kw φthe same with the weight left out (belt friction)
Vertical bendTout = (Tin − A sin αin − B cos αin) e−kφ + A sin αout + B cos αoutsee below
Weight correction factor, three cables cradledKw = 1 + (4/3) (d / (D − d))²statics of three circles side by side in a circle
Weight correction factor, three cables triangularKw = 1 / √(1 − (d / (D − d))²)statics of two circles on the wall carrying a third
Sidewall pressure, one cableP = T / Rthe sideways load of a cable under tension on a curve
Sidewall pressure, three cradledP = (3 Kw − 2) T / (3 R)the share of the middle cable
Sidewall pressure, three triangularP = Kw T / (2 R)the share of each of the two cables on the wall
Jam ratioJ = k D / d, with k = 1.05 by defaultthree cables can wedge when the conduit is about three cable diameters wide

Where the equations come from

One element of cable. Take a short length ds of cable sliding along the conduit. The tension rises along it by the part of its weight that has to be lifted plus the friction on whatever force n per unit length the wall puts on it: dT/ds = Wt sin α + μ Kw |n|, where α is the slope of the direction of pull. Every row of the table is this one equation with a different n.

  • In a straight the wall carries the weight across the slope, n = Wt cos α, which is constant: the tension rises in a straight line.
  • In a horizontal bend the tension pulls the cable against the inside of the curve with T/R per unit length, and the weight still presses down. The two are at right angles, so n = √((T/R)² + Wt²). Integrating gives the cosh and sinh form. When T is much larger than the weight of cable on one radius, Wt R, it becomes the capstan equation.
  • In a vertical bend the sideways pull of the tension and the weight act in the same plane: n = Wt cos α − σ T/R, where σ is +1 for a bend that turns the run upward (the foot of a riser) and −1 for one that turns it downward (the top of a riser), and the slope changes through the bend, α = αin + σ φ. While n keeps one sign s (+1 with the cable on the floor of the conduit, −1 with the tension holding it against the roof) the equation is linear and its solution is the form in the table with k = μ Kw s σ, A = 2 σ s μ Kw Wt R / (1 + (μ Kw)²) and B = −σ Wt R (1 − (μ Kw)²) / (1 + (μ Kw)²). The tool follows n through the bend and changes s where n passes through zero. The four cases usually listed separately (pulling up or down, concave up or down) are this one equation entered at different slopes.

A cable cannot push. On a steep falling stretch the equations can give a tension below zero. The cable then runs by itself; the tool holds the tension at zero until it rises again and marks the stretch as slack.

Three cables. Three equal cables do not rest on the conduit the way one does. Lying cradled, the two outer cables lean on the middle one; in a triangle, two cables on the wall are wedged apart by the third. In both cases the wall forces add up to more than the weight. Writing the equilibrium of each cable (weight down, wall force toward the conduit center, contact forces along the line joining the cable centers) gives the two factors in the table, with c = d / (D − d) the sine of the angle that fixes the geometry. In a bend the same statics applies with the sideways load T/R in place of the weight, which gives the sidewall pressure on the most loaded cable. The factor is then applied to the friction in bends as well as in straights, as cable pulling practice does.

How the run is entered

  • Rows go from end A to end B. Rising and falling are as walked from A to B; the tool mirrors them for the pull from B.
  • A horizontal bend has to sit in a level stretch. Left and right change the drawing, not the tension.
  • A vertical bend starts at the slope of the row before it and leaves at that slope plus or minus its angle. The straight after it has to continue at that slope: a 90 degree bend up from level is followed by a straight rising at 90 degrees.
  • Straights that do not touch a vertical bend may change slope from one row to the next without a bend between them, as hand calculations do.

What it assumes

  • A perfectly flexible cable: no force is needed to bend it into a curve or to straighten it afterwards.
  • One coefficient of friction for the whole run, the same in straights and bends, independent of the pressure on the wall and of speed.
  • The cables keep the chosen arrangement (cradled or triangular) all the way, and share the tension equally.
  • The incoming tension at the feed end is the same whichever end the cable is fed from.
  • Bends are circular arcs of the radius entered, and a horizontal bend lies in a level plane.
  • The sidewall pressure uses the highest tension in the bend, which is nearly always the tension leaving it.

When it misleads

  • The coefficient of friction is the weakest number. It varies with jacket, conduit, lubricant, temperature and wall pressure, and it sits in an exponent: in the figure's case, 0.45 in place of 0.35 raises the A to B tension by almost 90 percent.
  • Stiff cables. Large or armored cables resist bending. The extra force to feed them through a tight bend is not in these equations.
  • Low tension in a bend. The capstan form gives almost nothing where little tension arrives at a bend. The form with the cable weight does not, which is why the tool opens on it.
  • A jam is not a tension. If three cables wedge across the conduit in a bend the pull stops; no equation here predicts the force. The jam ratio only says whether the diameters invite it.
  • Slack stretches. Where the tool reports slack the cable is running ahead of the pull. The real tension there depends on how the reel is braked.
  • Allowables are not in the tool. The ratios on the page are only as good as the allowable tension and sidewall pressure typed in, which depend on the conductor, the cable construction and how the cable is gripped.

Common mistakes

  • Entering the bend angle in degrees in a hand calculation of eμKφ. The exponent needs radians: 90 degrees is 1.571.
  • Working one direction only. The reverse pull is the same arithmetic in the opposite order and can differ severalfold.
  • Adding the bends up: two 90 degree bends are not one 180 degree bend unless nothing lies between them, because the straight between them adds tension that the second bend multiplies.
  • Using the weight of one cable when three are pulled, or leaving out the weight correction factor in the exponent of the bends.
  • Taking the sidewall pressure from the tension entering the bend. It is the tension leaving that presses hardest.
  • Entering the radius of a bend to the inside of the conduit, or in inches where the equations take feet.
  • Treating a falling slope like a rising one. Downhill the weight term changes sign, and the tension can fall to zero.

Sources and checks

Every equation on this page is derived from the force balance above and was checked against an independent numerical integration of that balance (65 runs, both directions, agreement to better than one part in 100,000) and, for the three-cable factors, against a numerical solution of the equilibrium of the cables. The equations have the same form as those in cable makers' installation guides and in IEEE Std 1185, and the horizontal bend with cable weight and the vertical bend go back to Rifenburg (1953); those documents were not read for this page and are cited for the reader. The default jam band (2.8 to 3.2), the 1.05 ovality factor and the illustrative 500 lb/ft sidewall figure are numbers commonly printed in such guides, typed from memory: replace them with the figures of the guide that applies. No U.S. government manual with these equations was found.




References

Rifenburg, R. C. (1953). "Pipe-Line Design for Pipe-Type Feeders." Transactions of the American Institute of Electrical Engineers, Part III: Power Apparatus and Systems, Vol. 72, No. 2, pp. 1275–1288.

Institute of Electrical and Electronics Engineers. (2019). IEEE Recommended Practice for Cable Installation in Generating Stations and Industrial Facilities. IEEE Std 1185-2019, IEEE, New York.

Meriam, J. L., Kraige, L. G., and Bolton, J. N. (2018). Engineering Mechanics: Statics, 9th ed. Wiley, Hoboken, NJ.


DISCLAIMER: The methods and calculation on aNOWysis.com are provided as means to educate the reader. There is no warranty, expessed or implied, as to the relevance or accuracy of the methods or calculations. All calculations should be checked by a qualified analyst for appropriateness and accuracy. We will not be held liable for any damages, injuries or deaths caused by using methods or calculations from this site.