Tools › Building Systems › Lighting and Electrical › Cable Pulling Tension › Example

Three cables in a conduit three diameters wide: jam ratio 3.07, inside the band 2.8 to 3.2

ToolCable Pulling Tension
Sourceoriginal
LevelUndergraduate

Problem

Three cables of 1.05 in. diameter and 1.2 lb/ft each are pulled in a triangle through a conduit of 3.068 in. inside diameter: 120 ft, a 45 degree bend, 80 ft, a 45 degree bend the other way and 60 ft, bends of 3 ft radius, friction coefficient 0.35, incoming tension 30 lb. Find the jam ratio with a 1.05 ovality factor, the weight correction factor for both arrangements, and the tensions.

Inputs to Enter

  • Three cables triangular, cable diameter 1.05 in, weight 1.2 lb/ft each, conduit inside diameter 3.068 in, friction coefficient 0.35, incoming tension 30 lb
  • Rows: level 120 ft; horizontal bend left 45°, R 3 ft; level 80 ft; horizontal bend right 45°, R 3 ft; level 60 ft
  • Jam band 2.8 to 3.2 and ovality factor 1.05 (the page's defaults, typed from memory of cable pulling guides)
Open the Cable Pulling Tension tool

Answers

  • Jam ratio 1.05 × 3.068 / 1.05 = 3.07, inside the band 2.8 to 3.2 entered
  • Weight correction factor, triangular: 1/√(1 − (1.05/2.018)²) = 1.171; cradled the same cables would give 1.361
  • A to B: 207, 286, 404, 557, 646 lb at the ends of the five rows; B to A: 119, 164, 282, 389, 566 lb
  • Highest sidewall pressure: A to B (1.171/2) × 557/3 = 109 lb/ft at the second bend; B to A 75.9 lb/ft at the first bend of the table

Notes

Open this case in the tool: /analysis-tools/buildings/electrical/cable-pulling-tension/?try=three-cables-in-jam-band. The tensions are small in both directions; what the page reports here is that the diameters fall in the range where three cables can line up across the conduit and wedge in a bend. A jam is not predicted by any tension equation. Illustrative numbers.

More Examples for This Tool