A tight bend after 600 ft of straight conduit: tension at 27 % of the entry, sidewall pressure at 212 %

ToolCable Pulling Tension
Sourceoriginal
LevelProfessional

Problem

A single cable of 2.0 in. diameter weighing 4.5 lb/ft is pulled through 600 ft of level conduit, a 90 degree bend of 2 ft radius and a further 20 ft. The coefficient of friction is 0.4 and the incoming tension 50 lb. Compare the highest tension and the sidewall pressure at the bend, in each pull direction, with an allowable tension of 8,000 lb and an allowable sidewall pressure of 500 lb/ft typed in.

Inputs to Enter

  • One cable, diameter 2.0 in, weight 4.5 lb/ft, conduit inside diameter 5.047 in, friction coefficient 0.4, incoming tension 50 lb
  • Allowable tension 8,000 lb, allowable sidewall pressure 500 lb/ft (illustrative entries)
  • Rows: level 600 ft; horizontal bend left 90°, R 2 ft; level 20 ft
Open the Cable Pulling Tension tool

Answers

  • A to B: 50 + 0.4 × 4.5 × 600 = 1,130 lb entering the bend; 1,130 cosh(0.6283) + √(1,130² + 9²) sinh(0.6283) = 2,118 lb leaving it; 2,154 lb at B
  • Sidewall pressure of one cable, A to B: 2,118 / 2 = 1,059 lb/ft, 2.12 times the 500 lb/ft entered, while the tension is 0.27 of the 8,000 lb entered
  • B to A: 86 lb entering the bend, 162 lb leaving it, 1,242 lb at A; sidewall pressure 162 / 2 = 80.8 lb/ft, 0.16 of the entry

Notes

Open this case in the tool: /analysis-tools/buildings/electrical/cable-pulling-tension/?try=sidewall-pressure-governs. Sidewall pressure is the tension leaving a bend over its radius, so a bend that follows a long straight carries the load of the whole straight. Illustrative numbers; the allowables are typed in from the cable maker's data in practice.