Tools › Building Systems › Plumbing › Gas Pipe Sizing › Example
Propane after the second-stage regulator: 166,000 Btu/h through type L copper tube
| Tool | Gas Pipe Sizing |
| Source | Original illustrative system. Equation and factors: International Code Council (2021). International Fuel Gas Code, section 402.4, Equation 4-1 and Table 402.4 (C_r = 1.2462 for undiluted propane) (cited; no code table is reproduced). |
| Level | Undergraduate |
Problem
Propane at 11 in w.c. leaves a second-stage regulator into type L copper tube: trunk A 25 ft, branch B 10 ft to an 80,000 Btu/h furnace, trunk C 20 ft, branch D 5 ft to a 36,000 Btu/h water heater and branch E 15 ft to a 50,000 Btu/h range. Heating value 2,500 Btu/ft³ (a round typical figure), specific gravity 1.50, allowable drop 0.5 in w.c. Size the sections by the flow equation with the longest length method.
Inputs to Enter
- Propane, 2,500 Btu/ft³, specific gravity 1.50, inlet 11 in w.c., allowable drop 0.5 in w.c., copper tube type L, longest length method
- A from the regulator 25 ft; B from A 10 ft, 80,000 Btu/h; C from A 20 ft; D from C 5 ft, 36,000 Btu/h; E from C 15 ft, 50,000 Btu/h
Answers
- Longest run 25 + 20 + 15 = 60 ft; C_r = 0.00354 × 1.50 × 520 × (0.008/1.50)^0.152 = 1.2462
- Section A: 166,000 Btu/h ÷ 2,500 Btu/ft³ = 66.4 ft³/h; 3/4 in type L (D = 0.785 in) carries 82.2 ft³/h at 60 ft, 1/2 in (D = 0.545 in) only 31.5, so 3/4 in
- B and C 3/4 in (32.0 and 34.4 ft³/h); D and E 1/2 in (14.4 and 20.0 ft³/h)
- Pressure at the most remote outlet E by the equation: 11 − 0.228 = 10.77 in w.c.
Notes
Open this case in the tool: /analysis-tools/buildings/plumbing/gas-pipe-sizing/?try=propane-fits-smaller-tube. The same 166,000 Btu/h of natural gas (166 ft³/h) would need a larger trunk: propane carries about two and a half times the heat per cubic foot. The heating value is a typical figure typed from memory; use the supplier's. Whether copper tube is allowed for the gas is a question for the adopted code. Equation results only. Illustrative numbers; values from test_gas_pipe_sizing.php.
More Examples for This Tool
- Standby generator added to a house: the existing 1 in gas trunk against the fuel gas flow equation
- Longest length against branch length: a short gas branch near the meter comes out one size smaller
- A 400,000 Btu/h pool heater 250 ft from the meter: length takes the pipe from 1 in to 2 in
- A manufactured-home gas system: the federal capacity table of 24 CFR 3280.705(d) beside the flow equation