Tools › Building Systems › Plumbing › Gas Pipe Sizing › Example

A manufactured-home gas system: the federal capacity table of 24 CFR 3280.705(d) beside the flow equation

ToolGas Pipe Sizing
SourceU.S. Department of Housing and Urban Development (2026). Manufactured Home Construction and Safety Standards: Gas Piping Systems. Code of Federal Regulations, Title 24, Section 3280.705(d), table to paragraph (d), iron pipe sizes, 60 ft column. The piping layout is original and illustrative.
LevelProfessional

Problem

A manufactured home has a furnace (70,000 Btu/h), a range (50,000 Btu/h) and a water heater (30,000 Btu/h) on steel pipe: trunk A 20 ft, branch B 10 ft to the furnace, trunk C 30 ft, branches D and E 10 ft each to the range and the water heater. The regulation states a specific gravity of 0.65, 1,000 Btu/ft³ and a drop of 0.5 in w.c. Size the sections by the flow equation and compare each with the 60 ft column of the regulation's table (1 in: 260; 3/4 in: 138; 1/2 in: 66 thousand Btu/h).

Inputs to Enter

  • Natural gas, 1,000 Btu/ft³, specific gravity 0.65, inlet 7 in w.c., allowable drop 0.5 in w.c., Schedule 40 steel, longest length method
  • A from the inlet 20 ft; B from A 10 ft, 70,000 Btu/h; C from A 30 ft; D from C 10 ft, 50,000 Btu/h; E from C 10 ft, 30,000 Btu/h
  • Table Capacity column: A 260,000; B 138,000; C 138,000; D 66,000; E 66,000 Btu/h
Open the Gas Pipe Sizing tool

Answers

  • Longest run 60 ft; C_r at specific gravity 0.65 = 0.6522
  • Sizes by the equation: A 1 in (150,000 Btu/h against 249,600), B 3/4 in (70,000 against 132,400), C 3/4 in (80,000 against 132,400), D and E 1/2 in (50,000 and 30,000 against 63,300)
  • Every table value is at or above the demand of its section; each is 4.2 % above the equation capacity of the same size
  • At a specific gravity of 0.60 the equation is within 3.5 % of all 50 iron-pipe values of the table

Notes

Open this case in the tool: /analysis-tools/buildings/plumbing/gas-pipe-sizing/?try=federal-table-above-equation. The comparison column is the point of the page: type the capacity from the table that applies to your installation and it is set against the demand and the equation. The federal table applies to manufactured homes; elsewhere the adopted fuel gas code governs. Values from test_gas_pipe_sizing.php.

More Examples for This Tool