Tools › Building Systems › Plumbing › Gas Pipe Sizing › Example
A 400,000 Btu/h pool heater 250 ft from the meter: length takes the pipe from 1 in to 2 in
| Tool | Gas Pipe Sizing |
| Source | Original illustrative case. Equation: International Code Council (2021). International Fuel Gas Code, section 402.4, Equation 4-1 (cited; no code table is reproduced). |
| Level | Undergraduate |
Problem
A 400,000 Btu/h pool heater is fed by a single run of Schedule 40 steel pipe from the meter. Natural gas, 1,000 Btu/ft³, specific gravity 0.60, 7 in w.c. inlet, 0.5 in w.c. allowable drop. Find the smallest standard size by the flow equation for a 25 ft run and for a 250 ft run.
Inputs to Enter
- Natural gas, 1,000 Btu/ft³, specific gravity 0.60, inlet 7 in w.c., allowable drop 0.5 in w.c., Schedule 40 steel, one section with 400,000 Btu/h at its end
- Length 250 ft (the case on the page); change it to 25 ft for the comparison
Answers
- Flow 400,000 / 1,000 = 400 ft³/h
- 25 ft: 1 in pipe carries 415.6 ft³/h by the equation (3/4 in: 220.5), so 1 in; the drop is 0.466 in w.c.
- 250 ft: 1-1/2 in carries 368.4 ft³/h, less than 400; 2 in carries 709.8 ft³/h, so 2 in; the drop is 0.173 in w.c. and 6.83 in w.c. is left at the heater
- Capacity falls with length as L^−0.541: ten times the length leaves 29 % of the capacity of the same pipe
Notes
Open this case in the tool: /analysis-tools/buildings/plumbing/gas-pipe-sizing/?try=long-run-needs-two-inch. Equation results only: the adopted code table governs. Illustrative numbers; values from test_gas_pipe_sizing.php.
More Examples for This Tool
- Standby generator added to a house: the existing 1 in gas trunk against the fuel gas flow equation
- Longest length against branch length: a short gas branch near the meter comes out one size smaller
- A manufactured-home gas system: the federal capacity table of 24 CFR 3280.705(d) beside the flow equation
- Propane after the second-stage regulator: 166,000 Btu/h through type L copper tube