Tools › Building Systems › Plumbing › Gas Pipe Sizing › Example

Standby generator added to a house: the existing 1 in gas trunk against the fuel gas flow equation

ToolGas Pipe Sizing
SourceOriginal illustrative system. Equation: International Code Council (2021). International Fuel Gas Code, section 402.4, Equation 4-1 and the longest length method of section 402.4.1 (cited; no code table is reproduced).
LevelProfessional

Problem

A house has a 1 in Schedule 40 steel gas trunk (sections A, C and E: 20, 15 and 15 ft) feeding a furnace (80,000 Btu/h on 10 ft of 3/4 in), a water heater (40,000 Btu/h on 5 ft of 1/2 in), a range (65,000 Btu/h on 20 ft of 3/4 in) and a dryer (35,000 Btu/h on 10 ft of 1/2 in). A 300,000 Btu/h standby generator is added on a new 30 ft branch from the end of section A. Natural gas of 1,000 Btu/ft³ and specific gravity 0.60 arrives at 7 in w.c.; the allowable drop is 0.5 in w.c. What does the flow equation give for the existing trunk and for the new branch?

Inputs to Enter

  • Natural gas, heating value 1,000 Btu/ft³, specific gravity 0.60, inlet 7 in w.c., allowable drop 0.5 in w.c., Schedule 40 steel, longest length method
  • A from the meter 20 ft (installed 1 in); B from A 30 ft, 300,000 Btu/h (to be sized); C from A 15 ft (1 in); D from C 10 ft, 80,000 Btu/h (3/4 in)
  • E from C 15 ft (1 in); F from E 5 ft, 40,000 Btu/h (1/2 in); G from E 20 ft, 65,000 Btu/h (3/4 in); H from E 10 ft, 35,000 Btu/h (1/2 in)
Open the Gas Pipe Sizing tool (loaded with this example)

Answers

  • Longest run 20 + 15 + 15 + 20 = 70 ft (to outlet G); C_r = 0.00354 × 0.60 × 520 × (0.012/0.60)^0.152 = 0.6094
  • Section A carries 520,000 Btu/h = 520 ft³/h; 1 in pipe (D = 1.049 in) at 70 ft: Q = [19.17 × 1.049 × (0.5/(0.6094 × 70))^0.206]^(1/0.381) = 238.2 ft³/h, so the demand is 218 % of the equation capacity
  • Smallest standard size whose equation capacity meets 520 ft³/h at 70 ft: 1-1/2 in; the new branch B: 1-1/4 in (489.2 ft³/h against 300)
  • Sections C to H stay under their equation capacity (C: 220 against 238.2 ft³/h, 92 %)
  • Drop in A with the 1 in pipe: 0.6094 × 20 × (520^0.381/(19.17 × 1.049))^(1/0.206) = 0.605 in w.c.; pressure at outlet G 7 − 0.780 = 6.22 in w.c., a drop above the 0.5 in w.c. entered

Notes

Open this case in the tool: /analysis-tools/buildings/plumbing/gas-pipe-sizing/?try=trunk-over-equation-capacity (it is also the tool's opening default). Without the generator the same trunk carries 220 ft³/h, under its 238.2 ft³/h. These are results of the flow equation; the capacity tables of the adopted fuel gas code, the authority having jurisdiction and the makers' instructions govern, and the page is not a design approval. Illustrative numbers; values from test_gas_pipe_sizing.php.

More Examples for This Tool