Tools › Building Systems › Plumbing › Gas Pipe Sizing › Example
Longest length against branch length: a short gas branch near the meter comes out one size smaller
| Tool | Gas Pipe Sizing |
| Source | Original illustrative system. Methods: International Code Council (2021). International Fuel Gas Code, sections 402.4.1 (longest length) and 402.4.2 (branch length), with Equation 4-1 (cited; no code table is reproduced). |
| Level | Undergraduate |
Problem
A trunk A (10 ft) leaves the meter. At its end a 10 ft branch B feeds a 60,000 Btu/h appliance, and the trunk continues as C (40 ft) to a 10 ft branch D with 40,000 Btu/h and a 40 ft branch E with 100,000 Btu/h. Natural gas, 1,000 Btu/ft³, specific gravity 0.60, 7 in w.c. inlet, 0.5 in w.c. allowable drop, Schedule 40 steel. Size every section by the flow equation with the longest length method and with the branch length method.
Inputs to Enter
- Natural gas, 1,000 Btu/ft³, specific gravity 0.60, inlet 7 in w.c., allowable drop 0.5 in w.c., Schedule 40 steel
- A from the meter 10 ft; B from A 10 ft, 60,000 Btu/h; C from A 40 ft; D from C 10 ft, 40,000 Btu/h; E from C 40 ft, 100,000 Btu/h
Answers
- Longest run A + C + E = 90 ft; loads carried: A 200,000, C 140,000 Btu/h
- Longest length method (90 ft for every section): A 1 in, B 3/4 in, C 1 in, D 1/2 in, E 3/4 in
- Branch length method: B is sized with its own run A + B = 20 ft, where 1/2 in pipe carries 118.9 ft³/h by the equation against 60 ft³/h, so B is 1/2 in; D uses 60 ft (1/2 in carries 65.7 ft³/h); A, C and E are unchanged
- Pressure at the most remote outlet E by the equation: 7 − 0.344 = 6.66 in w.c.
Notes
Open this case in the tool: /analysis-tools/buildings/plumbing/gas-pipe-sizing/?try=branch-length-saves-a-size. The results table shows the size by both methods side by side. Equation results only: the adopted code table governs. Illustrative numbers; values from test_gas_pipe_sizing.php.
More Examples for This Tool
- Standby generator added to a house: the existing 1 in gas trunk against the fuel gas flow equation
- A 400,000 Btu/h pool heater 250 ft from the meter: length takes the pipe from 1 in to 2 in
- A manufactured-home gas system: the federal capacity table of 24 CFR 3280.705(d) beside the flow equation
- Propane after the second-stage regulator: 166,000 Btu/h through type L copper tube