Tools › Electrical and Controls › Power Systems › Unbalanced Fault Analysis › Example
Symmetrical components of an unbalanced set: 120 ∠ 0°, 105 ∠ −115°, 126 ∠ 122° V
| Tool | Unbalanced Fault Analysis |
| Source | original |
| Level | Undergraduate |
Problem
Three phase-to-neutral voltages are measured as Va = 120 ∠ 0° V, Vb = 105 ∠ −115° V and Vc = 126 ∠ 122° V. Find their zero-, positive- and negative-sequence components and the unbalance factors.
Inputs to Enter
- Entry: Phasor converter; phase a 120 at 0°, phase b 105 at −115°, phase c 126 at 122°
Answers
- V0 = (Va + Vb + Vc) / 3 = 4.889 ∠ 52.9° V
- V1 = (Va + a Vb + a² Vc) / 3 = 116.9 ∠ 2.2° V
- V2 = (Va + a² Vb + a Vc) / 3 = 8.416 ∠ −88.6° V
- Negative-sequence unbalance 8.416 / 116.9 = 7.20 %; zero-sequence unbalance 4.889 / 116.9 = 4.18 %
- Adding the three parts of each phase gives back 120 ∠ 0°, 105 ∠ −115° and 126 ∠ 122°
Notes
Open this case in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=unbalanced-voltages-in-three-sets. Illustrative numbers. The unbalance factors are ratios of sequence magnitudes; other definitions of unbalance give other numbers.
More Examples for This Tool
- Line-to-ground fault between two sources on a 138 kV bus: the sequence networks, and all of the ground current from one side
- A 100 Ω neutral resistor on a 115 kV transformer: the line-to-ground fault falls from 1,506 A to 607.5 A
- Solidly grounded generator terminals: the line-to-ground fault is 9/7 of the three-phase fault
- A grounded-wye / delta bank with no generator behind it supplies half of the ground current of a 69 kV fault
- Line-to-line fault from typed sequence impedances: 0.866 of the three-phase current when Z2 = Z1