Tools › Electrical and Controls › Power Systems › Unbalanced Fault Analysis › Example

Symmetrical components of an unbalanced set: 120 ∠ 0°, 105 ∠ −115°, 126 ∠ 122° V

ToolUnbalanced Fault Analysis
Sourceoriginal
LevelUndergraduate

Problem

Three phase-to-neutral voltages are measured as Va = 120 ∠ 0° V, Vb = 105 ∠ −115° V and Vc = 126 ∠ 122° V. Find their zero-, positive- and negative-sequence components and the unbalance factors.

Inputs to Enter

  • Entry: Phasor converter; phase a 120 at 0°, phase b 105 at −115°, phase c 126 at 122°
Open the Unbalanced Fault Analysis tool

Answers

  • V0 = (Va + Vb + Vc) / 3 = 4.889 ∠ 52.9° V
  • V1 = (Va + a Vb + a² Vc) / 3 = 116.9 ∠ 2.2° V
  • V2 = (Va + a² Vb + a Vc) / 3 = 8.416 ∠ −88.6° V
  • Negative-sequence unbalance 8.416 / 116.9 = 7.20 %; zero-sequence unbalance 4.889 / 116.9 = 4.18 %
  • Adding the three parts of each phase gives back 120 ∠ 0°, 105 ∠ −115° and 126 ∠ 122°

Notes

Open this case in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=unbalanced-voltages-in-three-sets. Illustrative numbers. The unbalance factors are ratios of sequence magnitudes; other definitions of unbalance give other numbers.