Tools › Electrical and Controls › Power Systems › Unbalanced Fault Analysis › Example
Line-to-ground fault between two sources on a 138 kV bus: the sequence networks, and all of the ground current from one side
| Tool | Unbalanced Fault Analysis |
| Source | original |
| Level | Undergraduate |
Problem
A 138 kV bus is fed from both sides. Left: a line (X1 = 12 Ω, X0 = 36 Ω), a 120 MVA 138 / 13.8 kV transformer (X = 0.10 pu, grounded wye on the 138 kV side, delta on the generator side) and a 120 MVA generator (X1 = 0.18, X2 = 0.16, X0 = 0.06 pu). Right: a line (X1 = 20 Ω, X0 = 60 Ω), an 80 MVA 138 / 34.5 kV transformer (X = 0.08 pu, delta on the 138 kV side) and a 200 MVA system equivalent at 34.5 kV (X1 = X2 = 0.20, X0 = 0.10 pu). On a 100 MVA base and with 1.0 pu prefault voltage, find the sequence impedances at the bus, the line-to-ground fault current and where the ground current comes from, and compare the four fault types.
Inputs to Enter
- Base 100 MVA, 138 kV at the fault; prefault voltage 1.0 pu; bolted fault; lines in ohms
- Left, from the bus outward: line X1 12 Ω, X0 36 Ω; transformer 0.10 pu on 120 MVA, 138 / 13.8 kV, Yg / Δ; source X1 0.18, X2 0.16, X0 0.06 pu on 120 MVA, 13.8 kV
- Right, from the bus outward: line X1 20 Ω, X0 60 Ω; transformer 0.08 pu on 80 MVA, 138 / 34.5 kV, Δ / Yg; source X1 0.20, X2 0.20, X0 0.10 pu on 200 MVA, 34.5 kV
Answers
- Base current 100 / (√3 × 138) = 418.4 A; base impedance 138² / 100 = 190.4 Ω
- Left: Z1 = j0.06301 + j0.08333 + j0.15 = j0.2963 pu, Z2 = j0.2797 pu, Z0 = j0.189 + j0.08333 = j0.2724 pu (the path ends at the grounded winding of the transformer)
- Right: Z1 = Z2 = j0.105 + j0.10 + j0.10 = j0.305 pu; zero sequence open at the delta winding
- At the fault: Z1 = j0.1503, Z2 = j0.1459, Z0 = j0.2724 pu
- Line-to-ground: I0 = I1 = I2 = 1 / (j0.1503 + j0.1459 + j0.2724) = 1.759 ∠ −90° pu; Ia = 3 I0 = 5.276 pu = 2,207 A; unfaulted phases at 1.12 pu
- Contributions in phase a: 1,493 A from the left and 714.6 A from the right; ground current 2,207 A from the left and none from the right; the right also carries 357.4 A in each of phases b and c
- Three-phase 2,783 A; line-to-line 2,446 A (0.879); double line-to-ground 2,597 A in the phases and 1,785 A in the ground; line-to-ground 0.793 of three-phase
Notes
The tool opens on this case; press Submit, or open it in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=ground-current-from-one-side. Illustrative numbers, not a real system. Currents are those arriving at the faulted bus; beyond the delta-wye transformers the phase currents differ. Checked against an independent phase-domain computation (test_unbalanced_fault_analysis.php).
More Examples for This Tool
- A 100 Ω neutral resistor on a 115 kV transformer: the line-to-ground fault falls from 1,506 A to 607.5 A
- Solidly grounded generator terminals: the line-to-ground fault is 9/7 of the three-phase fault
- A grounded-wye / delta bank with no generator behind it supplies half of the ground current of a 69 kV fault
- Line-to-line fault from typed sequence impedances: 0.866 of the three-phase current when Z2 = Z1
- Symmetrical components of an unbalanced set: 120 ∠ 0°, 105 ∠ −115°, 126 ∠ 122° V