Tools › Electrical and Controls › Power Systems › Unbalanced Fault Analysis › Example
Solidly grounded generator terminals: the line-to-ground fault is 9/7 of the three-phase fault
| Tool | Unbalanced Fault Analysis |
| Source | original |
| Level | Undergraduate |
Problem
A 100 MVA, 13.8 kV generator with X1 = X2 = 0.15 pu and X0 = 0.05 pu has a solidly grounded neutral. For a bolted fault at its terminals with 1.0 pu prefault voltage, find the currents of the four fault types and show which is the largest.
Inputs to Enter
- Base 100 MVA, 13.8 kV; prefault voltage 1.0 pu; one source: X1 0.15, X2 0.15, X0 0.05 pu, neutral solid
Answers
- Base current 4,184 A
- Three-phase: 1 / j0.15 = 6.667 pu = 27.89 kA
- Line-to-ground: I0 = 1 / (j0.15 + j0.15 + j0.05) = 2.857 pu; Ia = 8.571 pu = 35.86 kA, 9/7 = 1.286 of the three-phase current
- Line-to-line: I1 = 1 / j0.30 = 3.333 pu; Ib = √3 × 3.333 = 5.774 pu = 24.16 kA, 0.866 of three-phase
- Double line-to-ground: I1 = 1 / (j0.15 + j0.15 ∥ j0.05) = 5.333 pu, I2 = 1.333 pu, I0 = 4.00 pu; phases b and c 8.327 pu = 34.84 kA; ground current 3 I0 = 12 pu = 50.20 kA
- Unfaulted phases during the line-to-ground fault: 0.892 pu
Notes
Open this case in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=ground-fault-beats-three-phase. Illustrative numbers. The line-to-ground current is 3 V / (Z1 + Z2 + Z0) against V / Z1, so it is the larger whenever Z0 is below Z1 with Z2 = Z1.
More Examples for This Tool
- Line-to-ground fault between two sources on a 138 kV bus: the sequence networks, and all of the ground current from one side
- A 100 Ω neutral resistor on a 115 kV transformer: the line-to-ground fault falls from 1,506 A to 607.5 A
- A grounded-wye / delta bank with no generator behind it supplies half of the ground current of a 69 kV fault
- Line-to-line fault from typed sequence impedances: 0.866 of the three-phase current when Z2 = Z1
- Symmetrical components of an unbalanced set: 120 ∠ 0°, 105 ∠ −115°, 126 ∠ 122° V