Solidly grounded generator terminals: the line-to-ground fault is 9/7 of the three-phase fault

ToolUnbalanced Fault Analysis
Sourceoriginal
LevelUndergraduate

Problem

A 100 MVA, 13.8 kV generator with X1 = X2 = 0.15 pu and X0 = 0.05 pu has a solidly grounded neutral. For a bolted fault at its terminals with 1.0 pu prefault voltage, find the currents of the four fault types and show which is the largest.

Inputs to Enter

  • Base 100 MVA, 13.8 kV; prefault voltage 1.0 pu; one source: X1 0.15, X2 0.15, X0 0.05 pu, neutral solid
Open the Unbalanced Fault Analysis tool

Answers

  • Base current 4,184 A
  • Three-phase: 1 / j0.15 = 6.667 pu = 27.89 kA
  • Line-to-ground: I0 = 1 / (j0.15 + j0.15 + j0.05) = 2.857 pu; Ia = 8.571 pu = 35.86 kA, 9/7 = 1.286 of the three-phase current
  • Line-to-line: I1 = 1 / j0.30 = 3.333 pu; Ib = √3 × 3.333 = 5.774 pu = 24.16 kA, 0.866 of three-phase
  • Double line-to-ground: I1 = 1 / (j0.15 + j0.15 ∥ j0.05) = 5.333 pu, I2 = 1.333 pu, I0 = 4.00 pu; phases b and c 8.327 pu = 34.84 kA; ground current 3 I0 = 12 pu = 50.20 kA
  • Unfaulted phases during the line-to-ground fault: 0.892 pu

Notes

Open this case in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=ground-fault-beats-three-phase. Illustrative numbers. The line-to-ground current is 3 V / (Z1 + Z2 + Z0) against V / Z1, so it is the larger whenever Z0 is below Z1 with Z2 = Z1.