Tools › Electrical and Controls › Power Systems › Unbalanced Fault Analysis › Example
A grounded-wye / delta bank with no generator behind it supplies half of the ground current of a 69 kV fault
| Tool | Unbalanced Fault Analysis |
| Source | original |
| Level | Professional |
Problem
A 69 kV bus is fed from the left through a line (Z1 = 2 + j8 Ω, Z0 = 5 + j24 Ω) from a solidly grounded system equivalent (X1 = X2 = 0.05, X0 = 0.08 pu on 100 MVA). To the right a line (Z1 = 1.5 + j6 Ω, Z0 = 4 + j18 Ω) ends in a 30 MVA, 69 / 12.47 kV load transformer (X = 0.07 pu) with a grounded wye on the 69 kV side and a delta on the load side, and no generation. For a line-to-ground fault at the bus find the fault current and the current each side sends.
Inputs to Enter
- Base 100 MVA, 69 kV at the fault; prefault voltage 1.0 pu; bolted fault; lines in ohms
- Left: line X1 8, X0 24, R1 2, R0 5 Ω; source X1 0.05, X2 0.05, X0 0.08 pu on 100 MVA, 69 kV, neutral solid
- Right: line X1 6, X0 18, R1 1.5, R0 4 Ω; transformer 0.07 pu on 30 MVA, 69 / 12.47 kV, Yg / Δ; no source
Answers
- Base current 836.7 A; base impedance 47.61 Ω
- Positive and negative sequence: left side only, Z1 = Z2 = 0.04201 + j0.218 pu; the right side has no source and is open
- Zero sequence: left 0.105 + j0.5841 pu; right 0.08402 + j0.3781 + j0.2333 = 0.08402 + j0.6114 pu to the reference through the grounded winding; in parallel Z0 = 0.0475 + j0.2989 pu
- Line-to-ground: I0 = 1.339 ∠ −79.9° pu; Ia = 4.018 pu = 3,362 A, 0.892 of the 3,768 A three-phase current
- Ground current 3 I0: 1,714 A from the left and 1,649 A from the right
- Phase currents arriving from the right: 549.5 A in each of the three phases, in phase with each other (zero sequence only)
Notes
Open this case in the tool: /analysis-tools/electrical/power-systems/unbalanced-fault-analysis/?try=ground-current-without-a-generator. Illustrative numbers. The bank carries equal currents in all three phases although it has no source behind it.
More Examples for This Tool
- Line-to-ground fault between two sources on a 138 kV bus: the sequence networks, and all of the ground current from one side
- A 100 Ω neutral resistor on a 115 kV transformer: the line-to-ground fault falls from 1,506 A to 607.5 A
- Solidly grounded generator terminals: the line-to-ground fault is 9/7 of the three-phase fault
- Line-to-line fault from typed sequence impedances: 0.866 of the three-phase current when Z2 = Z1
- Symmetrical components of an unbalanced set: 120 ∠ 0°, 105 ∠ −115°, 126 ∠ 122° V