DOE handbook condenser: saturated steam at 40 °C condensed and subcooled to 30 °C

ToolThermodynamic Process Analyzer
SourceU.S. Department of Energy (1992). DOE Fundamentals Handbook: Thermodynamics, Heat Transfer, and Fluid Flow, Volume 1 of 3. DOE-HDBK-1012/1-92, U.S. Department of Energy, Washington, DC. Module HT-01, p. 67, Example 6 (Secondary Side of Heat Exchanger).
LevelUndergraduate

Problem

Steam flows through a condenser at 2.0 × 10⁶ kg/hr, entering as saturated vapor at 40 °C and leaving at the same pressure as subcooled liquid at 30 °C. Cooling water is available at 18 °C and may leave at 25 °C. Find the heat removed and the cooling water flow.

Inputs to Enter

  • Water and steam, heat exchanger side to a temperature; state 1 by temperature and quality: 40 °C, x = 1
  • Exit temperature 30 °C, mass flow 555.556 kg/s (2.0 × 10⁶ kg/hr)
Open the Thermodynamic Process Analyzer tool

Answers

  • h_1 = 2,573.54 kJ/kg (handbook 2,574), h_2 = 125.75 kJ/kg (handbook 125.8) at 7.384 kPa
  • Heat removed 2,447.8 kJ/kg, 1,359,900 kW (1,360 MW)
  • Cooling water enthalpy 75.6 kJ/kg at 18 °C and 104.9 kJ/kg at 25 °C (as printed), so the flow is 2.0 × 10⁶ · 2,447.8/29.3 = 1.67 × 10⁸ kg/hr (handbook 1.67 × 10⁸)

Notes

The tool does the steam side; the cooling water flow is the handbook's last step, done here by hand with the same two enthalpies. Using c_p ΔT for the steam would miss the condensation, which is almost all of the heat.