Tools › Building Systems › HVAC Equipment › Refrigerant Leak Rate › Example
A 20 lb walk-in cooler: a 2 lb top-up after 119 days is above 20 percent a year
| Tool | Refrigerant Leak Rate |
| Source | original |
| Level | Undergraduate |
Problem
A walk-in cooler in a restaurant holds 20 lb of refrigerant, above the 15 lb from which 40 CFR 84.106(a) applies. It received 1.5 lb on April 6, 2026 and 2 lb on August 3, 2026. Find the annualizing leak rate of 40 CFR 84.102 at each addition against the 20 percent for commercial refrigeration, and the date 30 days after the addition that is above it.
Inputs to Enter
- Appliance type commercial refrigeration, full charge 20 lb, threshold 20 %
- Service log: 2026-04-06, 1.5; 2026-08-03, 2 (pounds); method: annualizing
Answers
- April 6 (first addition, 365 days): 1.5/20 × 100 = 7.5 %
- August 3 (119 days since the last addition): 2/20 × 365/119 × 100 = 30.67 %, above 20 %
- By the rolling average method the same addition would be 3.5/20 × 100 = 17.5 %
- 30 days from August 3, 2026: September 2, 2026 (40 CFR 84.106(d) and (e)(1)); inspections once a year under 84.106(g)(1)(ii) for a charge under 500 lb
Notes
Open this case in the tool: /analysis-tools/buildings/equipment/refrigerant-leak-rate/?try=two-pound-top-up-crosses-20. Whether an appliance belongs to commercial refrigeration or to the exempt residential and light commercial air conditioning subsector is a question of the definitions in 40 CFR 84.102, outside the tool. Illustrative log; checked against an independent Python computation. Not legal advice.