Tools › Building Systems › HVAC Equipment › Refrigerant Leak Rate › Example
A cold room that takes 133 percent of its charge in one calendar year, with a follow-up verification test in the log
| Tool | Refrigerant Leak Rate |
| Source | original |
| Level | Professional |
Problem
A cold-storage appliance with a full charge of 300 lb received 90 lb on January 20, 2026 and 110 lb on March 17; a follow-up verification test on March 27 showed the identified leaks repaired; it then received 80 lb on June 9 and 120 lb on August 25. Find the leak rates by both methods of 40 CFR 84.102, the effect of the verification test on the rolling average, and the additions of the calendar year as a percentage of the full charge against the 125 percent of 40 CFR 84.106(j).
Inputs to Enter
- Appliance type commercial refrigeration, full charge 300 lb, threshold 20 %
- Service log: 2026-01-20, 90; 2026-03-17, 110; 2026-03-27, verified; 2026-06-09, 80; 2026-08-25, 120 (pounds); method: both
Answers
- Annualizing: 30.0 % (first addition), then 110/300 × 365/56 × 100 = 238.99 %, 80/300 × 365/84 × 100 = 115.87 %, 120/300 × 365/77 × 100 = 189.61 %
- Rolling average: 30.0 %, then 200/300 × 100 = 66.67 %; after the test of March 27 only later additions count: 80/300 × 100 = 26.67 %, then 200/300 × 100 = 66.67 %
- Every addition is above 20 % by both methods; 30 days from January 20, 2026 is February 19, 2026 (40 CFR 84.106(d))
- Calendar year 2026: 400/300 × 100 = 133.33 % of the full charge, at or over the 125 % of 40 CFR 84.106(j), which names March 1, 2027 for the report
Notes
Open this case in the tool: /analysis-tools/buildings/equipment/refrigerant-leak-rate/?try=over-125-in-one-year. The annualizing method does not use the verification test. The page takes the refrigerant added as the measure of the refrigerant leaked. Illustrative log; checked against an independent Python computation. Not legal advice.