Tools › Building Systems › HVAC Equipment › Refrigerant Leak Rate › Example

A comfort-cooling chiller that stays under 10 percent across two calendar years

ToolRefrigerant Leak Rate
Sourceoriginal
LevelUndergraduate

Problem

A chiller used for comfort cooling holds 800 lb of refrigerant. It received 20 lb on March 3, 2026, 25 lb on September 15, 2026 and 18 lb on April 20, 2027. Find the leak rate at each addition by both methods of 40 CFR 84.102 and compare it with the 10 percent of 40 CFR 84.106(c)(2)(iii).

Inputs to Enter

  • Appliance type comfort cooling, full charge 800 lb, threshold 10 %
  • Service log: 2026-03-03, 20; 2026-09-15, 25; 2027-04-20, 18 (pounds); method: both
Open the Refrigerant Leak Rate tool

Answers

  • March 3, 2026 (first addition, 365 days): 20/800 × 100 = 2.5 % by both methods
  • September 15, 2026 (196 days): annualizing 25/800 × 365/196 × 100 = 5.82 %; rolling 45/800 × 100 = 5.62 %
  • April 20, 2027 (217 days): annualizing 18/800 × 365/217 × 100 = 3.78 %; rolling 43/800 × 100 = 5.38 % (the March 2026 addition is more than 365 days back and has left the window)
  • No addition is above 10 %; additions are 5.62 % of the full charge in 2026 and 2.25 % in 2027

Notes

Open this case in the tool: /analysis-tools/buildings/equipment/refrigerant-leak-rate/?try=chiller-stays-under-10. The rolling window of the last addition starts on April 21, 2026, so it holds 25 + 18 = 43 lb. Illustrative log; checked against an independent Python computation. Not legal advice.

More Examples for This Tool