Tools › Building Systems › HVAC Equipment › Refrigerant Leak Rate › Example

One service log, two leak rates: the annualizing and rolling average methods on a supermarket rack

ToolRefrigerant Leak Rate
Sourceoriginal
LevelProfessional

Problem

A supermarket refrigeration rack with a full charge of 1,200 lb received 60 lb of refrigerant on February 10, 2026, 45 lb on May 12, 70 lb on July 21 and 95 lb on October 6. Find the leak rate at each addition by the annualizing method and by the rolling average method of 40 CFR 84.102, and the first addition at which each is above the 20 percent of 40 CFR 84.106(c)(2)(i).

Inputs to Enter

  • Appliance type commercial refrigeration, full charge 1,200 lb, threshold 20 %
  • Service log: 2026-02-10, 60; 2026-05-12, 45; 2026-07-21, 70; 2026-10-06, 95 (pounds); method: both, side by side
  • Additions counted from January 1, 2026 (40 CFR 84.106(a)(4))
Open the Refrigerant Leak Rate tool (loaded with this example)

Answers

  • First addition (365 days taken, 40 CFR 84.106(b)(1)): 60/1,200 × 365/365 × 100 = 5.0 % by both methods
  • May 12 (91 days since the last addition): annualizing 45/1,200 × 365/91 × 100 = 15.04 %; rolling 105/1,200 × 100 = 8.75 %
  • July 21 (70 days): annualizing 70/1,200 × 365/70 × 100 = 30.42 %, above 20 %; rolling 175/1,200 × 100 = 14.58 %, under it
  • October 6 (77 days): annualizing 95/1,200 × 365/77 × 100 = 37.53 %; rolling 270/1,200 × 100 = 22.5 %, above 20 %
  • 30 days from July 21, 2026, the period of 40 CFR 84.106(d): August 20, 2026; additions in calendar year 2026: 22.5 % of the full charge

Notes

The tool's default inputs are this case; press Submit, or open /analysis-tools/buildings/equipment/refrigerant-leak-rate/?try=two-methods-two-answers. Illustrative log, no real facility; checked against an independent Python computation with exact fractions. Regulation text read on 2026-11-21; the page states what that text gives for the log and is not legal advice.

More Examples for This Tool