Tools › Units › Calculators › Calc Sheet › Example
Heat loss through a three-layer wall: resistances in series, overall coefficient, watts and kWh per day
| Tool | Calc Sheet |
| Source | Original case; conductivities and film coefficients are entered illustrative values. |
| Level | Undergraduate |
Problem
A 12 m² wall of 13 mm gypsum board (0.16 W/m·K), 90 mm insulation (0.04 W/m·K) and 100 mm brick (0.72 W/m·K) separates air 25 K apart, with film coefficients of 8 and 25 W/m²·K. Find the overall coefficient, the heat loss and the energy lost in a day.
Inputs to Enter
- A = 12 m^2, DeltaT = 25 K, h_i = 8 W/(m^2-K), h_o = 25 W/(m^2-K), L_1 = 13 mm, k_1 = 0.16 W/(m-K), L_2 = 90 mm, k_2 = 0.04 W/(m-K), L_3 = 100 mm, k_3 = 0.72 W/(m-K)
- R_i = 1 / h_i in m^2-K/W, R_1 = L_1 / k_1 in m^2-K/W (and so on), R_t = R_i + R_1 + R_2 + R_3 + R_o
- U = 1 / R_t in W/(m^2-K); q = U * A * DeltaT in W; E_day = q * 24 h in kWh; check U < 0.5 W/(m^2-K)
Answers
- R_i = 0.1250, R_1 = 0.08125, R_2 = 2.250, R_3 = 0.1389, R_o = 0.04000, R_t = 2.635 m²·K/W
- U = 1 / 2.635 = 0.3795 W/(m²·K), below the 0.5 target: ratio 0.759, OK
- q = 0.3795 · 12 · 25 = 113.8 W; E_day = 113.8 W · 24 h = 2.732 kWh
- With US customary units chosen for the display: q = 388.5 Btu/h, E_day = 9,323 Btu
Notes
Open this case in the tool: /analysis-tools/units/calculators/calc-sheet/?try=wall-heat-loss. The insulation supplies 85 % of the resistance. The hour and the Btu are built on the sheet from the dictionary's kg/h and Btu/h entries, so no factor is typed.
More Examples for This Tool
- A tie rod in mixed units: 12 kN on a 0.5 in rod, stress in MPa and ksi, stretch in mm
- Bolted lap joint: bolt shear, plate bearing and the governing capacity with entered allowables
- Darcy-Weisbach pressure drop of 12 L/s in a 100 mm pipe with an entered friction factor
- A 180 kg machine on four 45 N/mm springs: static deflection, natural frequency and transmissibility