Tools › Structures › Statics › Cable Sag and Tension › Example

Power line conductor: catenary sag and tension of a 1,200-ft span (Bureau of Reclamation Example 4)

ToolCable Sag and Tension
SourceFarr, H. H. (1980). Transmission Line Design Manual. Water Resources Technical Publication, Water and Power Resources Service, U.S. Department of the Interior, Denver, CO. Example 4, p. 21; Figure 8, p. 17; Figure 10, p. 18.
LevelProfessional

Problem

A 795 kcmil ACSR 26/7 conductor weighing 1.0940 lb/ft hangs across a level 1,200-ft span with a horizontal tension of 4,137.83 lb (60 °F, no load). Find the sag, the tension at the supports and the conductor length, and compare the catenary with the parabola.

Inputs to Enter

  • Span 1,200 ft, supports level, cable weight 1.094 lb/ft, no deck load, no point load
  • Known: horizontal tension 4,137.83 lb; breaking strength 31,500 lb (rated breaking load of the conductor, Figure 10)
Open the Cable Sag and Tension tool

Answers

  • Sag at midspan 47.69 ft (book 47.690 ft); tension at each support 4,190 lb (book 4190 lb); catenary parameter H / w = 3,782.3 ft (book 3782.29 ft)
  • Conductor length 1,205.04 ft, 5.04 ft longer than the span; cable leaves each support 9.05° below the horizontal
  • Parabola for the same tension: sag 47.59 ft, 0.21 % low (the sag is 4 % of the span)
  • Breaking strength over largest static tension = 31,500 / 4,190 = 7.52

Notes

Open this case in the tool: /analysis-tools/structures/statics/cable-sag-tension/?try=power-line. The tool reproduces all fifteen sags of the manual's table (half spans of 100 to 1,500 ft) to the printed 0.001 ft, and the ten of the metric Example 3 to the printed millimeter. The manual's sag and tension work also covers stretch, creep, temperature, ice and wind, which this tool does not.

More Examples for This Tool