Unbalanced Fault Analysis: Method

Open the Unbalanced Fault Analysis tool

Unbalanced Fault Analysis: Sequence Networks from One-Line Data, Four Fault Types, Phase Currents and Voltages

The tool takes a power system as it is drawn on a one-line diagram, on either side of a faulted bus, builds its positive-, negative- and zero-sequence networks, and joins them the way each kind of short circuit requires. It then gives the phase currents in the fault, the phase voltages at the fault and the share of current that arrives from each side, for the three-phase, line-to-ground, line-to-line and double line-to-ground faults.

The idea: three balanced problems instead of one unbalanced one

A balanced three-phase circuit can be solved one phase at a time. A fault on one or two phases breaks the balance, and the phases can no longer be treated separately. Fortescue's observation (1918) was that any three phasors can be written as the sum of three sets that are each balanced:

  • a positive-sequence set: three equal phasors 120° apart in the order a-b-c, the order of normal operation;
  • a negative-sequence set: three equal phasors 120° apart in the order a-c-b;
  • a zero-sequence set: three equal phasors in phase with each other.

With the operator a = 1 ∠ 120° and phase a as the reference:

V0 = (Va + Vb + Vc) / 3     V1 = (Va + a Vb + a² Vc) / 3     V2 = (Va + a² Vb + a Vc) / 3

Va = V0 + V1 + V2     Vb = V0 + a² V1 + a V2     Vc = V0 + a V1 + a² V2

The same holds for currents. In a system whose three phases are built alike, a current of one sequence produces voltage drops of that sequence only, so each sequence has its own single-phase circuit: a sequence network. Only the positive-sequence network contains sources, because generators produce positive-sequence voltage. The fault is the one place where the three networks meet.

Building the three networks from the one-line diagram

Every element appears in each network with the impedance it offers to that sequence:

  • Line: Z1 = Z2; a larger Z0, because zero-sequence currents in the three conductors are in phase and return through the earth and ground wires.
  • Source (generator, motor or the equivalent of a larger system): X1 (the subtransient reactance for the first cycles), X2, and a smaller X0. The neutral carries Ia + Ib + Ic = 3 I0, so a neutral impedance Zn appears as 3 Zn in the zero-sequence network, and an ungrounded neutral opens it.
  • Transformer: its leakage reactance in the positive and negative networks. In the zero-sequence network the winding connections decide everything. Zero-sequence current can enter a winding only if it has a way back: through a grounded neutral, or by circulating inside a delta. Seen from the fault:
    • grounded wye / grounded wye: zero-sequence current passes through;
    • grounded wye toward the fault, delta away: the current flows from the fault through the grounded winding and circulates in the delta; the path ends here, at the reference, and nothing beyond takes part. Such a bank is a source of ground current even with no generator behind it;
    • delta toward the fault, or a wye whose neutral is not grounded: open.
One-line diagram of a two-source system with a fault between two lines, and below it the positive-, negative- and zero-sequence networks joined in series for a line-to-ground fault; the zero-sequence network is open at the delta winding of the right-hand transformer
Figure 1: The tool's opening case (illustrative numbers). Each element of the one-line diagram sits under itself in the three networks. The zero-sequence network ends at the grounded winding of T1 on the left and is open at the delta winding of T2 on the right.

Each side of the fault reduces to one impedance per sequence (the sum of its series elements), and the two sides are in parallel as seen from the fault. That gives the Thévenin impedances Z1, Z2 and Z0 at the fault.

Per unit and changes of base

Impedances are expressed as fractions of a base: Ibase = Sbase / (√3 Vbase), Zbase = Vbase² / Sbase, with Sbase the three-phase power and Vbase the line-to-line voltage. One power base serves the whole system; the voltage base changes at each transformer in the ratio of its rated voltages. Nameplate values are per unit on the equipment's own rating and are moved to the system base by

Znew = Zold × (Snew / Sold) × (Vold / Vnew)²

A line or a neutral resistor given in ohms is divided by the base impedance of the voltage zone it sits in.

The four connections

Each fault imposes conditions on the phase quantities at the fault point. Written in sequence components, the conditions say how the networks are joined (Vf is the voltage of phase a at the fault before the fault, Zf the fault impedance):

Four small diagrams: three-phase fault with the positive-sequence network alone; line-to-ground with the three networks in series; line-to-line with the positive and negative networks in parallel; double line-to-ground with all three in parallel
Figure 2: How the sequence networks are joined for each fault. The amber wires are the fault connection.
  • Three-phase: balanced, so positive sequence only. I1 = Vf / (Z1 + Zf).
  • Line-to-ground (phase a): Ib = Ic = 0 makes the three sequence currents equal, so the networks are in series. I0 = I1 = I2 = Vf / (Z1 + Z2 + Z0 + 3 Zf) and the fault current is Ia = 3 I0.
  • Line-to-line (b to c): no ground is involved, so I0 = 0, and I1 = −I2 = Vf / (Z1 + Z2 + Zf). The fault current is Ib = −j√3 I1. When Z2 = Z1 it is √3 / 2 = 0.866 of the three-phase current.
  • Double line-to-ground (b and c): the three networks are in parallel at the fault. I1 = Vf / (Z1 + Z2 ∥ (Z0 + 3 Zf)); it divides between the other two networks: I2 = −I1 (Z0 + 3 Zf) / (Z2 + Z0 + 3 Zf), I0 = −I1 Z2 / (Z2 + Z0 + 3 Zf). The current into the ground is Ib + Ic = 3 I0.

The sequence voltages at the fault follow from each network: V1 = Vf − I1 Z1, V2 = −I2 Z2, V0 = −I0 Z0, and the phase currents and voltages from the transformation above. The symbol ∥ means "in parallel with": x ∥ y = x y / (x + y), in complex numbers.

The line-to-ground current is 3 Vf / (Z1 + Z2 + Z0) against Vf / Z1 for the three-phase fault, so it is the larger of the two whenever Z0 is smaller than Z1 (with Z2 = Z1): at the terminals of a solidly grounded generator, or close to a grounded-wye / delta transformer. A neutral resistor or reactor is how that current is held down. With no zero-sequence path at all a line-to-ground fault draws no current, the faulted phase sits at ground potential and the other two rise to √3 times their normal voltage to ground.

Contribution from each side

In each sequence network the current at the fault divides between the left and right sides in inverse proportion to their impedances in that network. The zero-sequence division uses the zero-sequence paths, which are usually quite different from the others: a side can supply most of the ground current and little of the rest, or the reverse. The phase currents of a side are rebuilt from its three shares, which is why a side may carry current in a phase that has no current in the fault itself.

What it assumes

  • The three phases of every element are alike (transposed lines, symmetrical machines), so the sequence networks do not couple anywhere except at the fault.
  • No load current before the fault: every source has the prefault voltage behind its reactance, and all source voltages are in phase.
  • Constant impedances. With subtransient reactances the results are the initial symmetrical rms currents; the DC offset and the decay of machine currents are not modeled.
  • Transformer magnetizing branches, line charging and loads are left out; three-winding transformers, zigzag banks and autotransformers are not offered.
  • The system is two series chains that meet at the faulted bus, with at most four elements on a side. A meshed network needs a bus-impedance (Z-bus) program.
  • Phase a is the reference phase and the phase sequence is a-b-c.

When it misleads

  • Across a delta-wye transformer. The currents given for a side are those arriving at the faulted bus. On the other side of a delta-wye transformer the positive- and negative-sequence parts are shifted by 30° in opposite directions and the zero-sequence part does not appear, so the phase currents there have different magnitudes. The tool does not give them.
  • Zero-sequence data. The zero-sequence impedance of a line depends on earth resistivity, ground wires and neighboring circuits, and that of a three-legged core transformer is lower than its positive-sequence value. Blank zero-sequence cells are filled with the positive-sequence value and the page says so: for a line that is rarely true.
  • Breaker and equipment duty. Standards apply multipliers for the DC offset, X/R ratio and contact-parting time to currents like these. None is applied here.
  • Heavily loaded or weak systems, where the prefault currents and the angle between sources are not negligible.
  • High-resistance and arcing faults: a fault resistance can be entered, but an arc is not a constant resistance.

Common mistakes

  • Putting Zn instead of 3 Zn in the zero-sequence network (and Zf instead of 3 Zf for a ground fault).
  • Joining the networks of a double line-to-ground fault as Z1 ∥ (Z2 + Z0). The correct form is Z1 in series with Z2 ∥ Z0.
  • Carrying the zero-sequence network through a delta winding, or forgetting that a grounded-wye / delta bank closes it.
  • Reporting I0 as the line-to-ground fault current: the current in the faulted phase is 3 I0.
  • Mixing bases: using nameplate per-unit values without moving them to the common MVA base, or dividing ohms by the base impedance of the wrong voltage level.
  • Using the line-to-line voltage where the per-unit prefault voltage (line-to-neutral, 1.0) belongs.
  • Assuming the three-phase fault is always the largest.
  • Using the A-phase formulas for a fault on another phase without renaming the phases: the magnitudes are the same but the sequence currents are no longer in phase with each other.

How it was checked

The library reproduces the fault example of the MIT OpenCourseWare notes on symmetrical components (Kirtley, Section 7.4: currents through a breaker for the four faults on a two-source 138 kV system) and Examples 2 and 3 of the Schweitzer Engineering Laboratories tutorial (a generator with a step-up transformer and a neutral resistor; a two-source system with contributions and fault-point voltages) to their printed digits, with one exception stated in the test: the MIT notes print 6.43 per unit for the double line-to-ground phase current where their own formula and sequence currents give 6.34. Every case is also solved a second way, in the phase domain with the fault written as conditions on the phase voltages and currents, by an independent numerical script. Those two documents are cited for the method and used in the tests only; the cases offered on the page are original and illustrative.

Related tools

Voltage Drop and Short Circuit works radial building systems by the ohmic method. Protective Device Coordination plots device curves against fault currents such as these. Power Flow Solver gives the voltages and flows of the unfaulted network. Circuit Analysis solves any small network of impedances and sources with phasors.