Tools › Environmental › Spill Prevention › Secondary Containment Sizing › Example

Concrete dike around three oil tanks: net containment volume, percent of the largest tank and freeboard for rain (EPA SPCC guidance, Figure 4-6)

ToolSecondary Containment Sizing
SourceU.S. Environmental Protection Agency (2013). SPCC Guidance for Regional Inspectors. EPA 550-B-13-001, Office of Emergency Management, Washington, DC. Chapter 4, Figure 4-6, p. 4-22 (sample secondary containment calculations for multiple tanks in a containment area), with the rain event of Figure 4-5, p. 4-21; 40 CFR 112.8(c)(2).
LevelProfessional

Problem

A 60 ft × 36 ft concrete dike with walls 18 in (1.5 ft) tall surrounds one 20,000-gallon horizontal tank (10 ft diameter, 35 ft long) and two 10,000-gallon vertical tanks (each 10 ft in diameter). Find the total and the net capacity of the dike with the largest tank failed, the net capacity as a percent of the largest tank, and the depth of precipitation the remaining freeboard holds. Then find the wall height needed to hold the largest tank plus a 4.5-in rain.

Inputs to Enter

  • Containment: dike with vertical walls, length 60 ft, width 36 ft, wall height 1.5 ft
  • Tank 1: 20,000 gal, horizontal cylinder, diameter 10 ft, length 35 ft; Tanks 2 and 3: 10,000 gal each, vertical cylinders, diameter 10 ft; all on the floor, in this containment
  • Freeboard basis: design storm depth 4.5 in (the rain event of the guidance's Figure 4-5; an illustration, not a site value); no drainage area, no other displacement
Open the Secondary Containment Sizing tool (loaded with this example)

Answers

  • Total dike capacity 60 × 36 × 1.5 = 3,240 ft³: guidance 24,235 gal (with 7.48 gal/ft³), tool 24,237 gal (231 in³ per gallon)
  • Displacement of the two vertical tanks, 2 × π (10 ft)²/4 × 1.5 ft = 235.6 ft³: guidance 1,762 gal, tool 1,763 gal; the largest tank is not deducted
  • Net dike capacity: guidance 22,473 gal = 3,004 ft³, tool 22,474 gal = 3,004 ft³; 112 % of the largest tank (tool 112.4 %)
  • Available freeboard: guidance 2,473 gal = 331 ft³, a freeboard height of 0.15 ft ≈ 1.8 in; tool 2,474 gal, 1.84 in of precipitation
  • Tool only: with the 4.5-in rain the required volume is 26,059 gal (20,000 + 6,059), a shortfall of 3,585 gal; wall height needed 1.739 ft (20.9 in), or a length of 71.83 ft at the 1.5-ft wall; with a 10,000-gal tank failed the surplus is 5,362 gal

Notes

The tool's default inputs are this case; press Submit. The guidance's question is how much precipitation the dike holds (1.8 in), which the page reports as the precipitation depth the freeboard holds; set the storm depth to 0 to see the surplus equal the 2,474-gal freeboard. The one- or two-gallon differences come from the guidance's rounded 7.48 gal/ft³. Reproduced to the printed digits with that factor in test_secondary_containment.php, which also reproduces Figure 4-5 (wall heights 2.97, 3.27 and 3.35 ft) and the four worksheet examples of Appendix H. Whether the freeboard is sufficient is an engineering determination made by the person who certifies the SPCC Plan; the rule sets no storm.