Ventilation Rate: Method
Open the Ventilation Rate tool
ASHRAE 62.1 Ventilation Rate Procedure
Standard 62.1 sets the minimum outdoor air a space needs for acceptable indoor air quality as two parts: a people component that dilutes the contaminants occupants produce, Rp per person, and an area component for what the building and its furnishings emit, Ra per unit of floor area. The breathing-zone outdoor airflow is Vbz = Rp Pz + Ra Az. The rates come from the standard's Table 6-1 by occupancy category; the rows offered here are the common ones, and any category can be entered.
Not all the air delivered to a zone reaches the breathing zone. The zone air-distribution effectiveness Ez of Table 6-2 credits or penalizes the supply arrangement: 1.0 for cool air from the ceiling, 0.8 for warm air from the ceiling that short-circuits to a ceiling return, 1.2 for displacement ventilation from the floor. The zone outdoor airflow the system must deliver is Voz = Vbz / Ez.
For a single-zone system that is the outdoor-air intake. A multiple-zone recirculating system serves zones with different outdoor-air fractions Zp = Voz / Vpz, and the system intake follows from the critical zone by the standard's Appendix A; the tool reports Zp for the entered supply airflow as the input to that step. Local codes may adopt an earlier edition of the standard or different rates.